What is Merz Price Protection (Percentage Differential Protection) for Transformer and Generator (Alternator) ? Explain with Example?

TRANSFORMER 

1. Percentage Differential Protection for Transformers
       The percentage differential protection or Merz-Price protection based on the circulating current principle can also be used for the transformers. This system gives protection against phase to phase faults and phase to ground faults to the power transformers.
       The principle of such a protection scheme is the comparison of the currents entering and leaving the ends of a transformer. The vector difference of currents passes through the operating coil while the average current passes through the restraining coil. In normal conditions, the two currents at the two ends of the transformer are equal and balance is maintained. So no currents flow through the operating coil of the relay and and relay is inoperative. But when there is phase to phase fault or phase to ground fault, this balance gets disturbed. The difference current flows through the operating coil due to which relay operates, tripping the circuit breaker.
       Compared to the differential protection used in generators, there are certain important points which must be taken care of while using such protection for the power transformers. These points are,

1. In a power transformer, the voltage rating of the two winding is different. The high voltage winding is low current winding while low voltage winding is high current winding. Thus there always exists difference in current on the primary and secondary sides of the power transformer. Hence if C.T.s of same ratio are used on two sides, then relay may get operated through there is no fault existing.
       To compensate for this difficulty, the current ratios of C.T.s on each side are different. These ratios depend on the line currents of the power transformer and the connection of C.T.s. Due to the different turns ratio, the currents fed into the pilot wires from each end are same under normal conditions so that the relay remains inoperative. For example if K is the turns ratio of a power transformer then the ratio of C.T.s on low voltage side is made K times greater than that of C.T.s on high voltage side.

2. In case of power transformers, there is an inherent phase difference between the voltages induced in high voltage winding and low voltage winding. Due to this, there exists a phase difference between the line currents on primary and secondary sides of a power transformer. This introduces the phase difference between the C.T. secondary currents, on the two sides of a power transformer. Through the turns ratio of C.T.s are selected to compensate for turns ratio of transformer, a differential current may result due to the phase difference between the currents on two sides. Such a different current may operate the relay though there is no fault. Hence it is necessary to correct the phase difference.
       To compensate for this, the C.T. connections should be such that the resultant currents fed into the pilot wires from either sides are displaced in phase by an angle equal to the phase shift between the primary and secondary currents. To achieve this, secondaries of C.T.s on star connected side of a power transformer are connected in delta while the secondaries of C.T.s on delta connected side of a power transformer are connected in star.
       The table.1 gives the way of connecting C.T. secondaries for the various types of power transformer connections.

       With such an arrangement, the phase displacement between the currents gets compensated with the oppositely connected C.T. secondaries. Hence currents fed to the pilot wires from both the sides are in phase under normal running conditions and the relay is ensured to be inoperative.

3. The neutrals of C.T. star and power transformer stars are grounded.

4. Many transformers have tap changing arrangement due to which there is a possibility of flow of differential current. For this, the turns ratio of C.T.s on both sides of the power transformer are provided with tap for of C.T.s on both sides of the power transformer are provided with tap for their adjustment.
       For the sake of understanding, the connection of C.T. secondaries in delta for star side of power transformer and the connection of C.T. secondaries in star for delta side of power transformer is shown in the Fig.1(a) and (b).
Fig  1


1.1 Merz-Price Protection for Star-Delta Transformer
       Let us study the Merz-Price protection for the star-delta power transformer. The primary of the power transformer is star connected while the secondary is delta connected. Hence to compensate for the phase difference, the C.T. secondaries on primary side must be connected in delta while the C.T. secondaries on delta side must be connected in star. The star point of the power transformer primary as well as the star connected C.T. secondaries must be grounded.
        The circuit diagram of the scheme is shown in the Fig. 2.
Fig. 2  Merz-Price Protection for Star-Delta power transformer


       The restraining coils are connected across the C.T. secondary windings while the operating coils are connected between the tapping points on the restraining coils and the star point of C.T. secondaries.
       With the proper selection of turns ratio of C.T.s the coils are under balanced condition during normal operating conditions. The C.T. secondaries carry equal currents which are in phase under normal conditions. So no current flows through the relay and the relay is inoperative.
       With an internal fault in power transformer windings, the balance in the C.T.s get disturbed. The operating coils of differential relay carry currents proportional to the difference of current between the two sides of a power transformer. This causes the relay operation which trips the main circuit breakers on both the sides of the power transformer.
       The basic requirements of the differential relay are,
1. The differential relay must not operate on load or external faults.
2. It must operate on sever internal faults.
       The relay satisfying these requirements is used in Merz-Price protection.

       It is important to note that this scheme gives protection against short circuit faults between the turns i.e. interturn faults also. This is because when there is an interturn fault, the turns ratio of power transformer gets affected. Due to this the currents on both sides of the power transformer become unbalanced. This causes an enough differential current which floes through the relay and the relay operates.

1.2 Merz-Price Protection for Star-Star Transformer
       The Fig. 3 shows the Merz-Price protection system for the star-star power transformer. Both primary and secondary of the power transformer are connected in star and hence C.T. secondaries. The operating coils are connected between the tapping on the restraining coil and the ground. The operation of the scheme remains same for any type of power transformer as discussed for star-star power transformer.
Fig.  3   Merz-Price Protection for Star-Star power Transformer


Example : A three phase power transformer having a line voltage ratio of 400 V to 33 kV is connected in star-delta. the C.T.s on 400 V side have current ratio as 1000/5. What must be the C.T. ratio on 33 kV side.
       Assume current on 400 V side of transformer to be 1000 A.
Fig. 4

Solution : The arrangement is shown in the Fig. 4.
       On the primary side, which is 400 V side of transformer the current is 1000 A.
       Hence C.T.s primary will carry current of 1000 A.
       The C.T. ratio is 1000/5 on the primary side hence the current in C.T.
       Secondaries which is phase current of delta connected C.T.s is,
                  Ip = 1000 x (5/1000) = 5 A
       This is shown in the Fig.4
                   IL   =√3 Ip = 5√3 A
       This is balance the C.T. secondaries are connected in delta.

        The same current flows through the star connected C.T. secondaries. Hence each secondaries of C.T. on the secondary side of transformer carries a current of 5√3 A.
       For the power transformer the apparent power on both sides must be same.
       Primary apparent power = Secondary apparent power
                √3 VL1 IL1 = √3 VL2  IL2 
                √3 x 400 x 1000 = √3 x 33000 x IL2 
                IL2 = (400 x 1000)/33000 = 12.12 A

       Thus each primary of C.T.s connected in star carries a current of 12.12 A.while each secondary of C.T.s connected in star carries a current of 5√3 A.
       Hence the C.T. ratio on 33 kV side is,
       C.T. ratio = Primary current/Secondary current = 12.12/5√3 = 1.4 : 1
       This is the required C.T. ratio on 33 kV side.


GENERATOR (Alternator)

Merz-Price Protection of Alternator Stator Windings :

          This is most commonly used protection scheme for the alternator stator windings. The scheme is also called biased differential protection and percentage differential protection.
       In this method, the currents at the two ends of the protected section are sensed using current transformers. The wires connecting relay coils to the current transformer secondaries are called pilot wires.
       Under normal conditions, when there is no fault in the windings, the currents in the pilot wires fed from C.T. secondaries are equal. The differential current i1 - i2through the operating coils of the relay is zero. Hence the relay is inoperative and system is said to be balanced.
       When fault occurs inside the protected section of the stator windings, the differential current i1 - i2 flows through the operating coils of the relay. Due to this current, the relay operates. This trips the generators circuit breaker to isolate the faulty section. The is also disconnected and is discharged through a suitable impedance.
       The Fig.1 shows a schematic arrangement of Merz-Price protection scheme for a star connected alternator.

Fig. 1  Merz-Price protection for star connected alternator
       
        The differential relay gives protection against short circuit fault in the stator winding of a generator. The C.T.s are connected in star and are provided on both, the outgoing side and machine winding connections to earth side. The restraining coils are energized from the secondary connection of C.T.s in each phase, through pilot wires. The operating coils are energized by the tappings from restraining coils and the C.T. neutral earthing connection.
       The similar arrangement is used for the delta connected alternator stator winding. as shown in the Fig. 2.

Fig. 2  Merz-Price protection for delta connected alternator
       
       The C.T.s on the delta connected machine winding side are connected in delta while the C.T.s at outgoing ends are connected in star. The restraining coils are placed in each phase, energized by the secondary connections of C.T.s while the operating coils are energized from the restraining coil tappings and the C.T. neutral earthing.
       If there is a fault due to a short circuit in the protected zone of the windings, it produces a difference between the currents in the primary windings of C.T.s on both sides of the generator winding of the same phase. This results in a difference between the secondary currents pf the two currents transformers. Thus, under fault conditions, a differential current flows through the operating coils which is responsible to trip the relay and open the circuit breaker. The differential relay operation depends on the relation between the current in the operating coil and that in the restraining coil.
       
      In addition to the tripping of circuit breaker, the percentage differential relay trip a hand reset multi contact auxiliary relay. This auxiliary relay simultaneously initiates the following operations : - 

1. Tripping of the main circuit breaker of generator
2. Tripping of the field circuit breaker
3. Tripping of the neutral circuit breaker if it is present
4. Shut down of the prime mover
5. Turn on of CO2 gas if provided for safety of generator under faulty conditions.
6. Operation of alarm and / or annunciator to indicate the occurrence of the fault and the operation of the relay the field must be opened immediately otherwise it starts feeding the fault.
        When differential relaying is used for the protection, C.T.s at both the ends of generator must be of equal accuracy otherwise if the error is excessive, wrong operation of the relay may result. The cause of unequal currents on both the sides of C.T.s without any fault are ratio errors, unequal lengths of the leads, unequal secondary burdens etc.
       This scheme provides very fast protection to the stator winding against phase to phase faults and phase to ground faults. If the neutral is not grounded or grounded through resistance then additional sensitive earth fault relay should be provided.
       
              The advantages of this scheme are : 

1. Very high speed operation with operating time of about 15 msec.
2. It allows low fault setting which ensures maximum protection of machine windings.
3. It ensures complete stability under most severe through and external faults.
4. It does not require current transformers with air gaps or special balancing features.